Description
Monitors the APC hardware status such as APC External Environment Status, APC Integrated Environment Status, APC Environmental Management System Status, APC Rack Air Removal Unit Status, APC MasterSwitch Unit Status, APC MasterSwitch VM Unit Status, APC MasterSwitch Plus Unit Status, APC Automatic Transfer Switch(ATS) Status, APC NetworkAir FM System Status.
Prerequisites
SNMP should be enabled in end device and device should support PowerNet-MIB OIDs and SNMP credentials should be attached against the device in portal.
How to Apply: This template is All instance selection based. It will not ask user to select any instance (s) while assigning it to a device.
Metric Parameters
Parameter | Description |
---|---|
Frequency | Warning Threshold | If the metric value satisfies the condition defined along with Warning Threshold value, then a notification is sent to the user. |
Critical Threshold | If the metric value satisfies the condition defined along with Critical Threshold value, then a notification is sent to the user. |
Alert | The alert value can be set to either Yes or No. If it is Yes, then an alert message is sent to the user. |
Metrics
apc.airfmsys.input.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3, 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.4 |
Expression | if((airFMSysInputStatus!=airFMSysInputNormalState),airFMSysInputStatus,3) |
Description | Monitors the state of this contact: Open(1) or Closed(2). A violation will occur when this relay is not in its normal state. [OIDs: 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3, 1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Air FM System Input Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | NOT_EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"open"},{"2":"closed"},{"3":"normal"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.airfmsys.ouput.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2, 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3 |
Expression | if((airFMSysOutputStatus!=airFMSysOutputNormalState),airFMSysOutputStatus,3) |
Description | Monitors the state of this contact: Open(1) or Closed(2). A violation will occur when this relay is not in its normal state. [OIDs: 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2, 1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Air FM System Output Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | NOT_EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"open"},{"2":"closed"},{"3":"normal"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ems.alarm.device.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.17.1.1.3 |
Expression | NULL |
Description | Monitors the alarm device state. Possible values are 1- alarmDeviceOnEMS: device is active, 2- alarmDeviceOffEMS: device is inactive, 3- alarmDeviceNotInstalledEMS: device is not installed. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.17.1.1.2, 1.3.6.1.4.1.318.1.1.10.3.17.1.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Alarm Device State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"alarmDeviceOnEMS"},{"2":"alarmDeviceOffEMS"},{"3":"alarmDeviceNotInstalledEMS"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.ems.comm.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.12.2 |
Expression | NULL |
Description | Monitors the communication status between the agent and the Environment Management System (EMS). Possible values are 1- noComm: Communication has never been established, 2- comm: Communication has been established, 3- commLost: Communication was established, but was lost. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.12.1, 1.3.6.1.4.1.318.1.1.10.3.12.2] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Communication Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"noComm"},{"2":"comm"},{"3":"commLost"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.ems.input.contact.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.14.1.1.3 |
Expression | NULL |
Description | Monitors the state of the input contact. Possible values are 1- contactClosedEMS: input contact is closed, 2- contactOpenEMS : input contact state is open. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.14.1.1.2, 1.3.6.1.4.1.318.1.1.10.3.14.1.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Input Contact State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"contactClosedEMS"},{"2":"contactOpenEMS"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ems.outlet.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.16.1.1.3 |
Expression | NULL |
Description | Monitors the state of the outlet. Possible values are 1- outletOnEMS: outlet is on, 2- outletOffEMS: outlet is off. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.16.1.1.2, 1.3.6.1.4.1.318.1.1.10.3.16.1.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Outlet State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"outletOnEMS"},{"2":"outletOffEMS"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.ems.probe.comm.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.13.1.1.10 |
Expression | NULL |
Description | Monitors the state of communications to the probe. Possible values are 1- commsNeverDiscovered: indicates there has never been communications with this device, 2- commsEstablished: indicates communication is normal and active with this device, 3- commsLost: indicates communication had been established, but is no longer. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.13.1.1.2, 1.3.6.1.4.1.318.1.1.10.3.13.1.1.10] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Probe Communication Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"commsNeverDiscovered"},{"2":"commsEstablished"},{"3":"commsLost"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.ems.outrelay.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.15.1.1.3 |
Expression | NULL |
Description | Monitors the state of the output relay. Possible values are 1- relayClosedEMS: output relay is closed, 2- relayOpenEMS : output relay is open. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.15.1.1.2, 1.3.6.1.4.1.318.1.1.10.3.15.1.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Relay State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"relayClosedEMS"},{"2":"relayOpenEMS"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.ems.sensor.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.3.18.1.1.4 |
Expression | NULL |
Description | Monitors the sensor state. Possible values are 1- sensorFaultedEMS: sensor is faulted, 2- sensorOKEMS: sensor is not faulted, 3- sensorNotInstalledEMS: sensor is not installed. [OIDs: 1.3.6.1.4.1.318.1.1.10.3.18.1.1.3, 1.3.6.1.4.1.318.1.1.10.3.18.1.1.4] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC EMS Sensor State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"sensorFaultedEMS"},{"2":"sensorOKEMS"},{"3":"sensorNotInstalledEMS"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ext.envmon.probe.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.1.3.3.1.3 |
Expression | NULL |
Description | Monitors the connected status of the probe, either disconnected(1) or connected(2). [OIDs: 1.3.6.1.4.1.318.1.1.10.1.3.3.1.3, 1.3.6.1.4.1.318.1.1.10.1.3.3.1.2] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC External Environment Probe Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"disconnected"},{"2":"connected"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.integrated.envmon.probe.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3 |
Expression | NULL |
Description | Monitors the connected status of the probe, either disconnected(1) or connected(2). [OIDs: 1.3.6.1.4.1.318.1.1.10.2.3.2.1.2, 1.3.6.1.4.1.318.1.1.10.2.3.2.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Integrated Environment Probe Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"disconnected"},{"2":"connected"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.integrated.envmon.outrelay.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.2.3.7.1.3 |
Expression | NULL |
Description | Monitors the status of the output relay, either faultState(1) or normalState(2). [OIDs: 1.3.6.1.4.1.318.1.1.10.2.3.7.1.2, 1.3.6.1.4.1.318.1.1.10.2.3.7.1.3] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Integrated Environment Relay Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"faultState"},{"2":"normalState"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.masterswitchplus.outlet.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.6.7.1.1.2, 1.3.6.1.4.1.318.1.1.6.7.1.1.4, 1.3.6.1.4.1.318.1.1.6.7.1.1.5 |
Expression | sPDUOutletStatusMSPOutletState |
Description | Monitors the outlet state. If the outlet is on, the outletStatusMSPOn (1) value will be returned. If the outlet is off, the outletStatusMSPOff (2) value will be returned. [OIDs: 1.3.6.1.4.1.318.1.1.6.7.1.1.2, 1.3.6.1.4.1.318.1.1.6.7.1.1.4, 1.3.6.1.4.1.318.1.1.6.7.1.1.5] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC MasterSwitch Plus Outlet State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"outletStatusMSPOn"},{"2":"outletStatusMSPOff"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.masterswitchvm.current.load
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.5.4.2.1.6 |
Expression | NULL |
Description | Monitors the total amount of power being consumed by the load. It is represented as a percentage of full load. [OIDs: 1.3.6.1.4.1.318.1.1.5.4.2.1.2, 1.3.6.1.4.1.318.1.1.5.4.2.1.6] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC MasterSwitch VM Current Load |
Unit | % |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | GREATER_THAN_EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Warning Threshold | 90 | 0-100 |
Warning Repeat Count | 1 | 1-12 |
Critical Operator | GREATER_THAN_EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 95 | 0-100 |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.masterswitchvm.outlet.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.5.7.1.1.5, 1.3.6.1.4.1.318.1.1.5.7.1.1.2, 1.3.6.1.4.1.318.1.1.5.7.1.1.4 |
Expression | sPDUOutletStatusVMOutletState |
Description | Monitors the outlet state. If the outlet is on, the outletStatusOnVM (1) value will be returned. If the outlet is off, the outletStatusOffVM (2) value will be returned. [OIDs: 1.3.6.1.4.1.318.1.1.5.7.1.1.2, 1.3.6.1.4.1.318.1.1.5.7.1.1.4, 1.3.6.1.4.1.318.1.1.5.7.1.1.5] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC MasterSwitch VM Outlet State |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"outletStatusVMOn"},{"2":"outletStatusVMOff"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.aru.alarm.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.14.3.3.1.10 |
Expression | NULL |
Description | Monitors the current alarm state of the Air Removal Unit (ARU). If the state of the ARU is unknown, this variable is set to 'UNKNOWN'. It is an ASCII string containing the 8 flags. The flags are defined as follows: Flag 1: Fan Fail 1 Flag 2: Fan Fail 2 Flag 3: Fan Fail 3 Flag 4: Smoke (if ARU is equipped with smoke detector) Flag 5: High Temp (Out of Thermal Control) Flag 6: Over Temp (Exhaust Temp. Exceeds Override Setpoint) Flag 7: Fan Fail 4 (Gen 2 ARU only) Flag 8: Reserved. [OIDs: 1.3.6.1.4.1.318.1.1.14.3.3.1.2, 1.3.6.1.4.1.318.1.1.14.3.3.1.10] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Rack Air Removal Unit Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | NOT_INS | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 00000000,00000001 | |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | No | Yes/No |
Sample Output
No graph
apc.aru.comm.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.14.3.3.1.2 |
Expression | NULL |
Description | Monitors the state of communications to the device. Possible values are 1- commsNeverDiscovered: there has never been communications with this device, 2- commsEstablished: communication is normal and active with this device, 3- commsLost: communication had been established, but is no device. [OIDs: 1.3.6.1.4.1.318.1.1.14.3.3.1.2, 1.3.6.1.4.1.318.1.1.14.3.3.1.2] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Rack Air Removal Unit Status |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | NULL | Not Applicable |
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"commsNeverDiscovered"},{"2":"commsEstablished"},{"3":"commsLost"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ext.envmon.comm.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.10.1.3.1.0 |
Expression | NULL |
Description | Monitors the communication status between the agent and the Environmental Monitor. Possible values are 1- noComm: Communication has never been established, 2- comm: Communication has been established, 3- commLost: Communication was established, but was lost. [OID: 1.3.6.1.4.1.318.1.1.10.1.3.1.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"noComm"},{"2":"comm"},{"3":"commLost"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
apc.ats.comm.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.1.0 |
Expression | NULL |
Description | Monitors the current communication status of the Automatic Transfer Switch (ATS). Possible values are 1- atsNeverDiscovered, 2- atsCommEstablished, 3- atsCommLost. [OIDs: 1.3.6.1.4.1.318.1.1.8.5.1.1.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 3 | [{"1":"atsNeverDiscovered"},{"2":"atsCommEstablished"},{"3":"atsCommLost"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.redundancy.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.3.0 |
Expression | NULL |
Description | Monitors the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power source if the current source fails. atsFullyRedundant(2) indicates that the ATS will switch over to the alternate power source if the current source fails. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.3.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Warning Threshold | 1 | [{"1":"atsRedundancyLost"},{"2":"atsFullyRedundant"}] |
Warning Repeat Count | 1 | 1-12 |
Critical Operator | ||
Critical Threshold | ||
Critical Repeat Count | ||
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.over.current.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.4.0 |
Expression | NULL |
Description | Monitors the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allow a switch over to the alternate power source if the current source fails. atsCurrentOK(2) indicates that the output current is below the output current threshold. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.4.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"atsOverCurrent"},{"2":"atsCurrentOK"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.powersupply5v.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.5.0 |
Expression | NULL |
Description | Monitors the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial port Configuration Menu is not accessible . atsPowerSupplyOK(2) indicates that the ATS 5V power supply is operating within tolerance. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.5.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"atsPowerSupplyFailure"},{"2":"atsPowerSupplyOK"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.powersupply24v.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.6.0 |
Expression | NULL |
Description | Monitors the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.6.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"atsPowerSupplyFailure"},{"2":"atsPowerSupplyOK"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.sourceB.powersupply24v.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.7.0 |
Expression | NULL |
Description | Monitors the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the ATS is unable to switch over to the alternate power source if the current source fails. atsPowerSupplyOK(2) indicates that the ATS 24V power supply is operating within tolerance. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.7.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"atsPowerSupplyFailure"},{"2":"atsPowerSupplyOK"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.plus12v.powersupply.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.8.0 |
Expression | NULL |
Description | Monitors the state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS 12V power supply is operating within tolerance. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.8.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"atsPowerSupplyFailure"},{"2":"atsPowerSupplyOK"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.minus12v.powersupply.state
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.9.0 |
Expression | NULL |
Description | Monitors the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable to monitor the current sensors. atsPowerSupplyOK(2) indicates that the ATS -12V power supply is operating within tolerance. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.9.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"atsPowerSupplyFailure"},{"2":"atsPowerSupplyOK"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.switch.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.10.0 |
Expression | NULL |
Description | Monitors the status of the ATS. Possible values are 1- fail, 2- ok. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.10.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"fail"},{"2":"ok"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.sourceA.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.12.0 |
Expression | NULL |
Description | Monitors the status of the Source A. Possible values are 1- fail, 2- ok. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.12.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"fail"},{"2":"ok"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.sourceB.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.13.0 |
Expression | NULL |
Description | Monitors the status of the Source B. Possible values are 1- fail, 2- ok. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.13.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"fail"},{"2":"ok"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.phasesync.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.14.0 |
Expression | NULL |
Description | Monitors the status of the phase synch. Possible values are 1- inSync, 2- outOfSync. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.14.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 2 | [{"1":"inSync"},{"2":"outOfSync"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.vout.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.15.0 |
Expression | NULL |
Description | Monitors the output voltage status. Possible values are 1-fail, 2-ok. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.15.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"fail"},{"2":"ok"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.ats.hardware.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.8.5.1.16.0 |
Expression | NULL |
Description | Monitors the status of display board hardware. [OID: 1.3.6.1.4.1.318.1.1.8.5.1.16.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | ||
Warning Threshold | ||
Warning Repeat Count | ||
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 1 | [{"1":"fail"},{"2":"ok"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph
apc.airfmsys.present.status
Metric Details
Applicable for | Device |
SNMP OID | 1.3.6.1.4.1.318.1.1.13.1.4.1.2.0 |
Expression | NULL |
Description | Monitors the present mode of the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration. Possible values are 1- notApplicable, 2- reserved1, 3- reserved2, 4- onLine, 5- idle, 6- loadShare, 7- failed, 8- offLine. [OID: 1.3.6.1.4.1.318.1.1.13.1.4.1.2.0] |
Category | SNMP monitors |
Collector Type | Gateway |
Monitor Name | APC Status Monitors |
Unit |
Possible Inputs
Metric | Input Value | Range of Values |
---|---|---|
Frequency | 15 | 1 – 1440 (mins) |
Filter | ||
Warning Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Warning Threshold | 8 | [{"1":"notApplicable"},{"2":"reserved1"},{"3":"reserved2"},{"4":"onLine"},{"5":"idle"},{"6":"loadShare"},{"7":"failed"},{"8":"offLine"}] |
Warning Repeat Count | 1 | 1-12 |
Critical Operator | EQUAL | Ends with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with |
Critical Threshold | 7 | [{"1":"notApplicable"},{"2":"reserved1"},{"3":"reserved2"},{"4":"onLine"},{"5":"idle"},{"6":"loadShare"},{"7":"failed"},{"8":"offLine"}] |
Critical Repeat Count | 1 | 1-12 |
Alert | Yes | Yes/No |
Graph (Yes/No) | Yes | Yes/No |
Sample Output
No graph