Description

This template is used to monitor Chassis performance of B-Series Cisco UCS.

Prerequisites

Gateway should be up and running. Cisco UCS device should be reachable from Gateway. Chassis should be in managed state.

How to Apply: This template is All instance selection based. It will not ask user to select any instance (s) while assigning it to a device.

Metric Parameters

Metric Parameters
ParameterDescription
Frequency
  • Frequency is the interval in which you want to probe and collect metric data from the target device/resource
  • Frequency is defined in minutes (min).
  • Warning ThresholdIf the metric value satisfies the condition defined along with Warning Threshold value, then a notification is sent to the user.
    Critical ThresholdIf the metric value satisfies the condition defined along with Critical Threshold value, then a notification is sent to the user.
    AlertThe alert value can be set to either Yes or No. If it is Yes, then an alert message is sent to the user.

    Metrics

    ucs.sys.chassis.configstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines configstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2[{"0":"un-initialized"},{"1":"un-acknowledged"},{"2":"unsupported-connectivity"},{"3":"ok"},{"4":"removing"},{"6":"ack-in-progress"},{"7":"evaluation"},{"8":"acknowledged"},{"9":"auto-ack"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Eqipment Chassis Configstate

    Cisco UCS Eqipment Chassis Configstate

    ucs.sys.chassis.connstatus

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines connstatus state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning Operator
    Warning Threshold
    Warning Repeat Count1Manual
    Critical Operator
    Critical Threshold
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis Connstatus

    Cisco UCS EqipmentChassis Constatus

    ucs.sys.chassis.fsmstatus

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fsmstatus state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold14,18[{"0":"nop"},{"1":"DynamicReallocationBegin"},{"2":"DynamicReallocationConfig"},{"3":"DynamicReallocationFail"},{"4":"DynamicReallocationSuccess"},{"5":"RemoveChassisDecomission"},{"6":"RemoveChassisDisableEndPoint"},{"7":"RemoveChassisUnIdentifyLocal"},{"8":"RemoveChassisUnIdentifyPeer"},{"9":"PsuPolicyConfigBegin"},{"10":"PsuPolicyConfigExecute"},{"11":"RemoveChassisWait"},{"12":"PsuPolicyConfigFail"},{"13":"PsuPolicyConfigSuccess"},{"14":"RemoveChassisFail"},{"15":"RemoveChassisSuccess"},{"16":"PowerCapBegin"},{"17":"PowerCapConfig"},{"18":"PowerCapFail"},{"19":"PowerCapSuccess"},{"20":"RemoveChassisBegin"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis FSMstatus

    Cisco UCS EqipmentChassis FSMstatus

    ucs.sys.chassis.licstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines licstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4[{"0":"unknown"},{"1":"license-ok"},{"2":"license-insufficient"},{"3":"license-graceperiod"},{"4":"license-expired"},{"5":"not-applicable"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis LICstate

    Cisco UCS EqipmentChassis LICstate

    ucs.sys.chassis.operability

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines operability state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis Operability

    Cisco UCS EqipmentChassis Operablity

    ucs.sys.chassis.operstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines operstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis Operstate

    Cisco UCS EqipmentChassis Operstate

    ucs.sys.chassis.power

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines power state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold7[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,5,9,11[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis Power

    Cisco UCS EqipmentChassis Power

    ucs.sys.chassis.presence

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines presence state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold40[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold11,12,20,21,22,30[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis Presence

    Cisco UCS EqipmentChassis Presence

    ucs.sys.chassis.thermal

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines thermal state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-recoverable"},{"6":"lower-critical"},{"7":"lower-non-critical"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentChassis Thermal

    Cisco UCS EqipmentChassis Thermal

    ucs.sys.chassis.computeblade.operability

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines computeblade operability state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS ComputeBlade Operability

    Cisco UCS ComputeBlade Operability

    ucs.sys.chassis.computeblade.operpower

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines computeblade operpower state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold7[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS ComputeBlade Operpower

    Cisco UCS ComputeBlade Operpower

    ucs.sys.chassis.computeblade.operstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines computeblade operstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold0,5,8,10,13,15,16,17,21,26,27,29,30,31,1[{"0":"indeterminate"},{"1":"unassociated"},{"2":"ok"},{"3":"discovery"},{"4":"config"},{"5":"unconfig"},{"6":"power-off"},{"7":"restart"},{"8":"maintenance"},{"9":"test"},{"10":"compute-mismatch"},{"11":"compute-failed"},{"12":"degraded"},{"13":"discovery-failed"},{"14":"config-failure"},{"15":"unconfig-failed"},{"16":"test-failed"},{"17":"maintenance-failed"},{"18":"removed"},{"19":"disabled"},{"20":"inaccessible"},{"21":"thermal-problem"},{"22":"power-problem"},{"23":"voltage-problem"},{"24":"inoperable"},{"25":"decomissioning"},{"26":"bios-restore"},{"27":"cmos-reset"},{"28":"diagnostics"},{"29":"diagnostics-failed"},{"30":"pending-reboot"},{"31":"pending-reassociation"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold6,7,11,12,14,22,23,24,20[{"0":"indeterminate"},{"1":"unassociated"},{"2":"ok"},{"3":"discovery"},{"4":"config"},{"5":"unconfig"},{"6":"power-off"},{"7":"restart"},{"8":"maintenance"},{"9":"test"},{"10":"compute-mismatch"},{"11":"compute-failed"},{"12":"degraded"},{"13":"discovery-failed"},{"14":"config-failure"},{"15":"unconfig-failed"},{"16":"test-failed"},{"17":"maintenance-failed"},{"18":"removed"},{"19":"disabled"},{"20":"inaccessible"},{"21":"thermal-problem"},{"22":"power-problem"},{"23":"voltage-problem"},{"24":"inoperable"},{"25":"decomissioning"},{"26":"bios-restore"},{"27":"cmos-reset"},{"28":"diagnostics"},{"29":"diagnostics-failed"},{"30":"pending-reboot"},{"31":"pending-reassociation"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS ComputeBlade Operstate

    Cisco UCS ComputeBlade Operstate

    ucs.sys.chassis.computeblade.presence

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines computeblade presence state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold40[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold11,12,20,21,22,30[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS ComputeBlade Presence

    Cisco UCS ComputeBlade Presence

    ucs.sys.chassis.fanmodule.fan.operability

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fanmodule fan operability state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Fan Operability

    Cisco UCS Fan Operability

    ucs.sys.chassis.fanmodule.fan.operstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fanmodule fan operstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Fan Operstate

    Cisco UCS Fan Operstate

    ucs.sys.chassis.fanmodule.fan.power

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fanmodule fan power state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold7[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,5,9,11[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Fan Power

    Cisco UCS Fan Power

    ucs.sys.chassis.fanmodule.fan.thermal

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fanmodule fan thermal state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-recoverable"},{"6":"lower-critical"},{"7":"lower-non-critical"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Fan Thermal

    Cisco UCS Fan Thermal

    ucs.sys.chassis.fanmodule.fan.voltage

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fanmodule fan voltage state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-critical"},{"6":"lower-critical"},{"7":"lower-non-recoverable"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Fan Voltage

    Cisco UCS Fan Voltage

    ucs.sys.chassis.fanmodule.fan.presence

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines fanmodule fan presence state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold40[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold11,12,20,21,22,30[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS Fan Presence

    Cisco UCS Fan Presence

    ucs.sys.chassis.psu.operability

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines psu operability state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentPsu Operability

    Cisco UCS EqipmentPsu Operability

    ucs.sys.chassis.psu.operstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines psu operstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentPsu Operstate

    Cisco UCS EqipmentPsu Operstate

    ucs.sys.chassis.psu.power

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines psu power state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold7[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,5,9,11[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentPsu Power

    Cisco UCS EqipmentPsu Power

    ucs.sys.chassis.psu.presence

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines psu presence state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold40[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold11,12,20,21,22,30[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentPsu Presence

    Cisco UCS EqipmentPsu Presence

    ucs.sys.chassis.psu.thermal

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines psu thermal state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-recoverable"},{"6":"lower-critical"},{"7":"lower-non-critical"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentPsu Thermal

    Cisco UCS EqipmentPsu Thermal

    ucs.sys.chassis.psu.voltage

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines psu voltage state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-critical"},{"6":"lower-critical"},{"7":"lower-non-recoverable"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentPsu Voltage

    Cisco UCS EqipmentPsu Voltage

    ucs.sys.chassis.equipmentiocard.adminpowerstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard adminpowerstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning Operator
    Warning Threshold
    Warning Repeat Count1Manual
    Critical Operator
    Critical Threshold
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    No graph

    ucs.sys.chassis.equipmentiocard.configstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard configstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNone
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2[{"0":"un-initialized"},{"1":"un-acknowledged"},{"2":"unsupported-connectivity"},{"3":"ok"},{"4":"removing"},{"6":"ack-in-progress"},{"7":"evaluation"},{"8":"acknowledged"},{"9":"auto-ack"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Configstate

    Cisco UCS EqipmentIOCard Configstate

    ucs.sys.chassis.equipmentiocard.fsmstatus

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard fsmstatus state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold14,18[{"0":"nop"},{"1":"DynamicReallocationBegin"},{"2":"DynamicReallocationConfig"},{"3":"DynamicReallocationFail"},{"4":"DynamicReallocationSuccess"},{"5":"RemoveChassisDecomission"},{"6":"RemoveChassisDisableEndPoint"},{"7":"RemoveChassisUnIdentifyLocal"},{"8":"RemoveChassisUnIdentifyPeer"},{"9":"PsuPolicyConfigBegin"},{"10":"PsuPolicyConfigExecute"},{"11":"RemoveChassisWait"},{"12":"PsuPolicyConfigFail"},{"13":"PsuPolicyConfigSuccess"},{"14":"RemoveChassisFail"},{"15":"RemoveChassisSuccess"},{"16":"PowerCapBegin"},{"17":"PowerCapConfig"},{"18":"PowerCapFail"},{"19":"PowerCapSuccess"},{"20":"RemoveChassisBegin"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard FsmStatus

    Cisco UCS EqipmentIOCard FsmStatus

    ucs.sys.chassis.equipmentiocard.operability

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard operability state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Operability

    Cisco UCS EqipmentIOCard Operability

    ucs.sys.chassis.equipmentiocard.operstate

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard operstate state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold51, 106[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,8,14,82,104,105,108[{"0":"unknown"},{"1":"operable"},{"2":"inoperable"},{"3":"degraded"},{"4":"powered-off"},{"5":"power-problem"},{"6":"removed"},{"7":"voltage-problem"},{"8":"thermal-problem"},{"9":"performance-problem"},{"10":"accessibility-problem"},{"11":"identity-unestablishable"},{"12":"bios-post-timeout"},{"13":"disabled"},{"14":"malformed-fru"},{"51":"fabric-conn-problem"},{"52":"fabric-unsupported-conn"},{"81":"config"},{"82":"equipment-problem"},{"83":"decomissioning"},{"84":"chassis-limit-exceeded"},{"100":"not-supported"},{"101":"discovery"},{"102":"discovery-failed"},{"103":"identify"},{"104":"post-failure"},{"105":"upgrade-problem"},{"106":"peer-comm-problem"},{"107":"auto-upgrade"},{"108":"link-activate-blocked"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Operstate

    Cisco UCS EqipmentIOCard Operstate

    ucs.sys.chassis.equipmentiocard.power

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard power state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold7[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,5,9,11[{"0":"unknown"},{"1":"on"},{"2":"test"},{"3":"off"},{"4":"online"},{"5":"offline"},{"6":"offduty"},{"7":"degraded"},{"8":"power-save"},{"9":"error"},{"10":"ok"},{"11":"failed"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Power

    Cisco UCS EqipmentIOCard Power

    ucs.sys.chassis.equipmentiocard.presence

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard presence state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold40[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold11,12,20,21,22,30[{"0":"unknown"},{"1":"empty"},{"10":"equipped"},{"11":"missing"},{"12":"mismatch"},{"13":"equipped-not-primary"},{"20":"equipped-identity-unestablishable"},{"21":"mismatch-identity-unestablishable"},{"22":"equipped-with-malformed-fru"},{"30":"inaccessible"},{"40":"unauthorized"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Presence

    Cisco UCS EqipmentIOCard Presence

    ucs.sys.chassis.equipmentiocard.thermal

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard thermal state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-recoverable"},{"6":"lower-critical"},{"7":"lower-non-critical"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Thermal

    Cisco UCS EqipmentIOCard Thermal

    ucs.sys.chassis.equipmentiocard.voltage

    Metric Details

    Metric Details
    Applicable forDevice
    DescriptionIt defines equipmentiocard voltage state of chassis
    CategoryUCS
    Collector TypeGateway
    Monitor NameCisco UCS B-Series Chassis Performance
    UnitNULL

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorNONE
    Warning Threshold
    Warning Repeat Count1Manual
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,3,4,5,6,7[{"0":"unknown"},{"1":"ok"},{"2":"upper-non-recoverable"},{"3":"upper-critical"},{"4":"upper-non-critical"},{"5":"lower-non-critical"},{"6":"lower-critical"},{"7":"lower-non-recoverable"},{"100":"not-supported"}]
    Critical Repeat Count1Manual
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    Cisco UCS EqipmentIOCard Voltage

    Cisco UCS EqipmentIOCard Voltage