Description

Template to monitor Xtreme Unidirectional Protection System (XUPS). Monitors battery capacity, battery current, battery voltage, battery time remaining, environment temperature, output load, input frequency, output frequency, battery status (ABM) and Ambient Temperature. Can be applied on all the XUPS devices.

Prerequisites

SNMP should be enabled in end device and device should support XUPS-MIB OIDs and SNMP credentials should be attached against the device in portal.

Metric Parameters

Metric Parameters
ParameterDescription
Frequency
  • Frequency is the interval in which you want to probe and collect metric data from the target device/resource
  • Frequency is defined in minutes (min).
  • Warning ThresholdIf the metric value satisfies the condition defined along with Warning Threshold value, then a notification is sent to the user.
    Critical ThresholdIf the metric value satisfies the condition defined along with Critical Threshold value, then a notification is sent to the user.
    AlertThe alert value can be set to either Yes or No. If it is Yes, then an alert message is sent to the user.

    Metrics

    xups.environment.ambient.temperature

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.6.1.0
    ExpressionNULL
    DescriptionProvides the Xtreme Unidirectional Protection System (XUPS) reading of the ambient temperature in the vicinity of the UPS or SNMP agent. Alert will get generated when the value is not equal to zero.
    [OID: 1.3.6.1.4.1.534.1.6.1].
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Environment Temperature
    UnitC

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold28
    0 - 2147483647
    Warning Repeat Count11-12
    Critical OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold32
    0 - 2147483647
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Environment Ambient Temperature

    XUPS Environment Ambient Temperature

    xups.environment.remote.temperature

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.6.5.0
    ExpressionNULL
    DescriptionProvides the XUPS reading of a remote temperature sensor connected to the UPS or SNMP agent.
    [OID: 1.3.6.1.4.1.534.1.6.5].
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Environment Temperature
    UnitC

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold32
    0 - 2147483647
    Warning Repeat Count11-12
    Critical OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold35
    0 - 2147483647
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Environment Remote Temperature

    XUPS Environment Remote Temperature

    xups.output.load

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.4.1.0
    ExpressionNULL
    DescriptionThe UPS output load in percent of rated capacity. Monitor failure indicates that the percentage load attached to the UPS has been exceeded. The output load affects the running time of all components being supplied battery power. [OID: 1.3.6.1.4.1.534.1.4.1.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Output Load
    Unit%

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold800-100
    Warning Repeat Count11-12
    Critical OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold900-100
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Output Load

    XUPS Output Load

    xups.battery.abm.status

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.2.5.0
    ExpressionNULL
    DescriptionThe status of the Advanced Battery Management. [OID: 1.3.6.1.4.1.534.1.2.5.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Battery Status (ABM)
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorNOT_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold4[{"1":"batteryCharging"},{"2":"batteryDischarging"},{"3":"batteryFloating"},{"4":"batteryResting"},{"5":"unknown"},{"6":"batteryDisconnected"},{"7":"batteryUnderTest"},{"8":"checkBattery"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    xups.output.status

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.4.5.0
    ExpressionNULL
    DescriptionThe present source of output power. [OID: 1.3.6.1.4.1.534.1.4.5.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Output Status
    UnitNone

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold4[{"1":"other"},{"2":"none"},{"3":"normal"},{"4":"bypass"},{"5":"battery"},{"6":"booster"},{"7":"reducer"},{"8":"parallelCapacity"},{"9":"parallelRedundant"},{"10":"highEfficiencyMode"},{"11":"maintenanceBypass"}]
    Warning Repeat Count11-12
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold2,5[{"1":"other"},{"2":"none"},{"3":"normal"},{"4":"bypass"},{"5":"battery"},{"6":"booster"},{"7":"reducer"},{"8":"parallelCapacity"},{"9":"parallelRedundant"},{"10":"highEfficiencyMode"},{"11":"maintenanceBypass"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)NoYes/No

    Sample Output

    No graph

    xups.battery.capacity

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.2.4.0
    ExpressionNULL
    DescriptionProvides the XUPS battery percent charge. [OID: 1.3.6.1.4.1.534.1.2.4]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Battery Statistics
    Unit%

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorLESS_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold500-100
    Warning Repeat Count11-12
    Critical OperatorLESS_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold250-100
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Battery Capacity

    XUPS Battery Capacity

    xups.battery.current

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.2.3.0
    ExpressionNULL
    DescriptionProvides the Xtreme Unidirectional Protection System (XUPS) battery current as reported by the UPS metering. Current is positive when discharging, negative when recharging the battery. Alert will get generated when the value is greater than equal to 30. [OID: 1.3.6.1.4.1.534.1.2.3.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Battery Statistics
    Unitamps

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold25
    0..4294967295
    Warning Repeat Count11-12
    Critical OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold30
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Battery Current

    XUPS Battery Current

    xups.battery.voltage

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.2.2.0
    ExpressionNULL
    DescriptionBattery voltage as reported by the UPS meters. Monitor failure indicates a problem with the voltage being supplied to end devices. There may not be enough voltage presently being provided to attached devices. As a result, devices may not operate as expected. [OID: 1.3.6.1.4.1.534.1.2.2.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Battery Statistics
    Unitv

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorRANGEEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold116125
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Battery Voltage

    XUPS Battery Voltage

    xups.battery.time.remaining

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.2.1.0
    ExpressionNULL
    DescriptionProvides the XUPS battery run time in seconds before UPS turns off due to low battery.
    [OID: 1.3.6.1.4.1.534.1.2.1].
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS Battery Statistics
    Units

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning OperatorLESS_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold650
    0..4294967295
    Warning Repeat Count11-12
    Critical OperatorLESS_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold600
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Battery Time Remaining

    XUPS Battery Time Remaining

    xups.input.frequency

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.3.1.0
    ExpressionxupsInputFrequency/10
    DescriptionThe utility line frequency in tenths of Hz. Monitor failure indicates that the power being supplied to devices is fluctuating. Devices may be susceptible to problems with receiving power at varying frequencies.
    [OID: 1.3.6.1.4.1.534.1.3.1.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS I/O Frequency
    UnitHz

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorRANGEEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold551650
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Input Frequency

    XUPS Input Frequency

    xups.output.frequency

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.534.1.4.2.0
    ExpressionxupsOutputFrequency/10
    DescriptionThe measured UPS output frequency in tenths of Hz. Monitor failure indicates that the power being supplied to devices is fluctuating. Devices may be susceptible to problems when receiving power at varying frequencies. Note: This configuration assumes that 60 Hz is nominal. Non-North American countries may have different nominal frequencies. As well, if your equipment is very sensitive, the range of acceptable values should be adjusted accordingly. [OID: 1.3.6.1.4.1.534.1.4.2.0]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameXUPS I/O Frequency
    UnitHz

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    Filter
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical OperatorRANGEEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold551650
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    XUPS Output Frequency

    XUPS Output Frequency