Description

Template to monitor Liebert PDU parameters like system status, power source neutral current,receptacle branch real power, receptacle branch apparent power, receptacle branch electrical current (SysObjId:1.3.6.1.4.1.476.1.42).

Prerequisites

SNMP should be enabled in end device and device should support LIEBERT-GP-PDU-MIB and SNMP credentials should be attached against the device in portal.

How to Apply: This template is All instance selection based. It will not ask user to select any instance(s) while assigning it to a device.

Metric Parameters

Metric Parameters
ParameterDescription
Frequency
  • Frequency is the interval in which you want to probe and collect metric data from the target device/resource
  • Frequency is defined in minutes (min).
  • Warning ThresholdIf the metric value satisfies the condition defined along with Warning Threshold value, then a notification is sent to the user.
    Critical ThresholdIf the metric value satisfies the condition defined along with Critical Threshold value, then a notification is sent to the user.
    AlertThe alert value can be set to either Yes or No. If it is Yes, then an alert message is sent to the user.

    Metrics

    liebert.pdu.system.status

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.476.1.42.3.8.20.1.25
    ExpressionNULL
    DescriptionIt monitors the PDU system status[LIEBERT-GP-PDU-MIB :: lgpPduEntrySysStatus -1.3.6.1.4.1.476.1.42.3.8.20.1.25]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameLiebert PDU System Health
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorEQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold8[{"1":"normalOperation"},{"2":"startUp"},{"8":"normalWithWarning"},{"16":"normalWithAlarm"},{"32":"abnormalOperation"}]
    Warning Repeat Count11-12
    Critical OperatorIN_LISTEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold16, 32
    [{"1":"normalOperation"},{"2":"startUp"},{"8":"normalWithWarning"},{"16":"normalWithAlarm"},{"32":"abnormalOperation"}]
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    No graph

    liebert.pdu.powersource.neutral.current

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.476.1.42.3.8.30.20.1.70
    ExpressionlgpPduPsEntryEcNeutral/10
    DescriptionIt measures the neutral current at the PDU's power source in Amperes RMS (Root Mean Squared) [LIEBERT-GP-PDU-MIB :: lgpPduPsEntryEcNeutral - 1.3.6.1.4.1.476.1.42.3.8.30.20.1.70]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameLiebert PDU Power Source
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold75
    0..4294967295
    Warning Repeat Count11-12
    Critical OperatorGREATER_THANEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold80
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    No graph

    liebert.pdu.receptacle.branch.real.power

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.476.1.42.3.8.40.20.1.115
    ExpressionNULL
    DescriptionIt gives the line-to-neutral measurement of the Real Power [LIEBERT-GP-PDU-MIB :: lgpPduRbEntryPwr - 1.3.6.1.4.1.476.1.42.3.8.40.20.1.115]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameLiebert PDU Receptacle Branch
    UnitW

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    No graph

    liebert.pdu.receptacle.branch.apparent.power

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.476.1.42.3.8.40.20.1.120
    ExpressionNULL
    DescriptionIt gives the line-to-neutral measurement of the Apparent Power(VoltAmp) [LIEBERT-GP-PDU-MIB :: lgpPduRbEntryAp - 1.3.6.1.4.1.476.1.42.3.8.40.20.1.120]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameLiebert PDU Receptacle Branch
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning Operator
    Warning Threshold
    Warning Repeat Count
    Critical Operator
    Critical Threshold
    Critical Repeat Count
    AlertNoYes/No
    Graph (Yes/No)YesYes/No

    Sample Output

    No graph

    liebert.pdu.receptacle.branch.electrical.current

    Metric Details

    Metric Details
    Applicable forDevice
    SNMP OID1.3.6.1.4.1.476.1.42.3.8.40.20.1.130
    ExpressionlgpPduRbEntryEcHundredths/100
    DescriptionIt gives the line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared) [LIEBERT-GP-PDU-MIB :: lgpPduRbEntryEcHundredths - 1.3.6.1.4.1.476.1.42.3.8.40.20.1.130]
    CategorySNMP monitors
    Collector TypeGateway
    Monitor NameLiebert PDU Receptacle Branch
    Unit

    Possible Inputs

    Possible Inputs
    MetricInput ValueRange of Values
    Frequency51 – 1440 (mins)
    FilterNULLNot Applicable
    Warning OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Warning Threshold80
    0..4294967295
    Warning Repeat Count11-12
    Critical OperatorGREATER_THAN_EQUALEnds with, ==, !=, >=, <=, >, <, In Range, Out of range, Equals, Not equals, Equals Ignore Case, Not Equals Ignore Case, Contains, Not contains, Regex match, Regex no match, In string list, Not in string list, In List, Not in list, Starts with
    Critical Threshold90
    0..4294967295
    Critical Repeat Count11-12
    AlertYesYes/No
    Graph (Yes/No)YesYes/No

    Sample Output